CENTRIFUGAL JET FAN 300ºC/2h
MANUFACTURING FEATURES
Centrifugal powerful jet fan with low profile conceived for car parkings, working inside
the hazardous area and remove wide air volume in car parks 300ºC/2h.
FAN
• Galvanized steel sheet casing.
• Strong backward impeller with self-cleaning system made of strong galvanized steel sheet.
• External wiring box.
• Inlet protection.
• Feet included.
MOTOR
• Class H insulation, S1 continuous use and S2 emergency use, with bearing balls,
IP-55 protection, 2 speeds.
• 400V 4/8 poles Dalhander three phase motor.
• Maximum working temperature:
• S1 -> -20ºC +60ºC.
• S2 -> 300ºC / 2h.
| Fan sheet | ||
| Fan type | Jet fan | |
| Installation category | E - Free inlet and free outlet conditions, and without a partition between the inlet and outlet areas | |
| Efficiency category | Static | |
| VF | A variable speed drive is not required | |
| Motor power (kW) | 2,2/0,37 | |
| Requirements 2026 | Values | |
| Max. efficiency (%) | 33.65 | 46.71 |
| Efficiency grade (N) | 47.5 | 60.56 |
| Maximum efficiency point data | ||
| Flow (m³/h) | 4540.85 | |
| Static pressure (Pa) | 994.6 | |
| Speed (rpm) | 1430 | |
| Absorbed power (kW) | 2.748 | |
| Specific ratio | 1.00 | |