CENTRIFUGAL JET FAN 400ºC/2h
MANUFACTURING FEATURES
Centrifugal powerful jet fan with low profile conceived for car parkings, working inside
the hazardous area and remove wide air volume.
It is 400ºC/2h and 300ºC/2h.
FAN
• Galvanized steel sheet casing.
• Strong backward impeller with self-cleaning system made of strong galvanized steel sheet.
• External wiring box.
• Inlet protection.
• Feet included.
MOTOR
• Class H insulation, S1 continuous use and S2 emergency use, with bearing balls,
IP-55 protection, 2 speeds.
• 400V 4/8 poles Dalhander three phase motor.
• Maximum working temperature:
• S1 -> -20ºC +60ºC.
• S2 -> 400ºC / 2h.
A | B | C | D | E | F | H | I | K | L | Thrust (N) |
---|---|---|---|---|---|---|---|---|---|---|
1600 | 300 | 1000 | 351,5 | 1093 | 1052 | 800 | 250 | 13 | 4 | 97/25 |
MANUFACTURING FEATURES
• Support of great radial and axial elasticity.
• These low-profile, compact and elastic supports control the three directions of movement with large deformations in the rubber.
• It consists of two parallel armour adhered to the bell-shaped rubber and by a base with handles.
• These supports with handles have a threaded hole in their upper frame and are easy to install and fix.
• The steel protection washer allows it to withstand overloads by increasing its rigidity and protects the rubber from dripping hydrocarbons.
• Elastomer type NR or high quality elastomer. Working temperatures between -40ºC and + 70º C.
• Taking into account the tolerances of hardness in the elastomers, the mechanical characteristics of these series may differ.
• Range of 6 sizes and 3 different hardnesses (45-60-75) to fit a load range between 2 Kg and 1300 Kg.
1. Soft: hardness A 45
2. Average: hardness B 60
3. Hard: hardness C 75
APPLICATIONS
• Very appropriate in the elastic suspensions of machines that present vibrations of horizontal components.
MANUFACTURING FEATURES
• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:
Arrow (mm.) r.p.m.
20 mm >600 r.p.m.
30 mm >500 r.p.m.
• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.
APPLICATION
• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
MANUFACTURING FEATURES
• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.
*Dial panel incorporated. Optional EMC filter.
Certifications: CE/UL/CSA/EN/GOST/CCC.
Protection index IP20.
The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.
Variador de frecuencia para grupo garaje 230: Entrance 230V I, exit 230V III
Variador de frecuencia para grupo garaje 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current
Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.